Features
- Quick connect solution for permanent generator load bank testing and a backup portable generator
- Mechanically interlocked mechanism prevents cross-connecting power sources
- Dry contacts provided for annunciator circuit
- Disconnects are 3-pole circuit breakers as standard (optional 4-pole breakers or molded case switches available)
- Type 3R freestanding 12 gauge galv. steel enclosure with gray powdercoat RAL 7035 (stainless steel & additional colors optional)
- Color-coded cam style connectors for easy back-up generator & load bank connection
- Dual side wireway extension for top and/or bottom conduit entry/exit
- Hinged plates secure generator cord entries when not in use
- Operating instructions on inside of enclosure
- Ground fault protection option available
- NEC 700.12 compliant
- Accepts 24VDC signal from ATS to switch power during load bank testing (other signal trip voltages available)
Approvals
- NRTL Listed assembly
- UL 1691 Listed receptacles
- UL 489 Listed/CSA certified molded case circuit breaker
- UL 1087 Listed molded case switch
Drawings
If you are a specifying engineer and require a drawing of this item for your current project you can:
Request Drawing Here!